Air Efficiency Module
MP-F series
Energy Monitor Main Unit MP-FEA1
*Please note that accessories depicted in the image are for illustrative purposes only and may not be included with the product.
Specifications
Model | MP-FEA1 | |||
Measurement specifications | Phase wire system | 1-phase 2-wire, 1-phase 3-wire, 3-phase 3-wire, 3-phase 4-wire (switchable) | ||
No. of measurement circuits | 1 circuit (maximum of 2 circuits in a 1-phase 2-wire configuration *1) | |||
Input specifications | Primary side rated current (In) | Dedicated MP-FEC100 CT: 100 A, or general-purpose CT (secondary side rated input current 1 A) *2 | ||
Overcurrent withstand capability | 1.2 times the primary side rated current (can be continuous), 10 times the primary side rated current (1 sec or less) | |||
Rated input voltage | 1-phase 2-wire | When using MP-FEC100/MP-FEC250/MP-FEC600 or general-purpose CT: 100 VAC to 277 VAC (L-N) | ||
1-phase 3-wire | When using MP-FEC100/MP-FEC250/MP-FEC600 or general-purpose CT: 100 VAC to 240 VAC (L-N), 200 VAC to 480 VAC (L-L) | |||
3-phase 3-wire | When using MP-FEC100/MP-FEC250/MP-FEC600 or general-purpose CT: 173 VAC to 480 VAC (L-L) | |||
3-phase 4-wire | When using MP-FEC100/MP-FEC250/MP-FEC600 or general-purpose CT: 100 to 277 VAC (L-N), 173 to 480 VAC (L-L) | |||
Maximum allowable earth voltage | When using MP-FEC100/MP-FEC250/MP-FEC600 or general-purpose CT: 480 VAC to earth | |||
Input voltage fluctuation range constant | -15% to +15% of rated input voltage | |||
Rated input frequency | 50/60 Hz | |||
Displayable range | Voltage | Display resolution: 0.1 [V] | ||
Current | Display resolution: 0.001 [A] | |||
Active power/Reactive power/Apparent power | -8942.400 to +8942.400 [kW/kvar/kVA], Display resolution: 0.001 [kW/kvar/kVA] | |||
Active energy/Reactive energy/Apparent energy | 0.000 to 999999.999 [kWh/kvarh/kVAh], Display resolution: 0.001 [kWh/kvarh/kVAh] | |||
Power factor (PF) | -1.00 to 1.00, Display resolution: 0.01 | |||
Frequency | 0.0 to 90.0 [Hz], Display resolution: 0.1 [Hz] | |||
Measurement accuracy | Voltage | ±0.5% of RD (within rated input voltage) *3 | ||
Current | ・When using MP-FEC100/MP-FEC250/MP-FEC600 or general-purpose CT: ±0.5% of RD (5% ≤ In ≤ 120%), ±1.0% of RD (1% ≤ In < 5%) *2 *3 | |||
Active energy | ・When using MP-FEC100/MP-FEC250/MP-FEC600 or general-purpose CT: Complies with IEC62053-22 §7.9 table 3 class 0.5 *2 *3 | |||
Reactive energy | ・When using MP-FEC100/MP-FEC250/MP-FEC600 or general-purpose CT: Complies with IEC62053-23 §7.9 table 3 class 2 *2 *3 | |||
Apparent energy | ・When using MP-FEC100/MP-FEC250/MP-FEC600 or general-purpose CT: ±0.5% of RD (5% ≤ In ≤ 120%), ±1.0% of RD (1% ≤ In < 5%) *2 *3 *4 | |||
Effects of ambient temperature | ±0.03%/K *3 *5 | |||
Effects of harmonics | ±0.5% of RD *3 *6 | |||
Power factor (PF) | ±0.01 *3 | |||
Frequency | ±0.1 [Hz] *3 | |||
Current consumption | 36 mA | |||
Withstand voltage | Between all terminals and case: 2500 VAC for 1 minute | |||
Insulation resistance | Between all terminals and case: at least 20 MΩ min (500 VDC), Between voltage measurement terminals | |||
Environmental resistance | Ambient temperature | -5 to +55°C (no freezing) | ||
Relative humidity | 35 to 85% RH (no condensation) | |||
Measurement category | ll | |||
Usage altitude | 2500 m or less | |||
Pollution degree | 2 | |||
Installation method | DIN rail | |||
Vibration resistance | 10 to 500 Hz; Power Spectral Density: 0.033 G2/Hz for X, Y and Z directions | |||
Shock resistance | 150 m/s2, 2 times each for X, Y, and Z directions | |||
Material | Polycarbonate | |||
Weight | Approx. 110 g | |||
*1 When measuring two circuits, use the same voltage and phase for the two circuits to be measured. Also, use CT of the same model. |